Bas Chatel, University of Amsterdam, bastiaan.chatel@gmail.com
Lesli Dao, University of Amsterdam, l.dao@hotmail.com
Wessel de Jong, University of Amsterdam, wes_dejong9@hotmail.com
Gosia Migut, University of
Amsterdam, mmigut@gmail.com
Student Team: Yes
Visualizations in D3 developed by
the undergraduate student team for the course Minor Programming: Programming
Project at the University of Amsterdam.
Adobe Illustrator
Approximately how
many hours were spent working on this submission in total?
480
May we post your
submission in the Visual Analytics Benchmark Repository after VAST Challenge
2016 is complete? Yes
Video
https://staff.fnwi.uva.nl/m.a.migut/UVA-Migut-MC2.wmv
Questions
MC2.1 What are
the typical patterns visible in the prox card
data? What does a typical day look like for GAStech employees?
Limit your response to no more than 6 images and 500 words.
The prox data is fairly
regular. The detections follow daily patterns and on the weekends that are very
few to none detections. On the Saturday 4th of June there was not a
single detection for the whole building. We describe the observed patterns for
the general data, for each floor and separately for the weekends.
Figure MC2.1_1. In the big view
a daily pattern (3 a.m. 3 a.m.) of the amount of detections for the three
floors; in the overview below the pattern over the two weeks period.
·
Figure MC2.1_1 shows the daily
pattern of the amount of detections for the three floors. There are always the
most people present on the second floor, the least on the third floor. There
are people leaving the first floor at 9 a.m. and just before 3 p.m., but it
seems they are not going to other floors (not more people detected on other
floors at those time stamps).
·
The 1st floor has
three peaks during the day, see figure 2.
The employees start coming in around 5:30 a.m. with a peak at 7 a.m.
Then around 9 a.m. most of them are gone from the floor 1, followed by
increased amount of detection with a peak at 12 p.m. Then again they leave the
floor, with the lowest amount of detections around 2:15 p.m. followed by
increase with a peak just before 4p.m. Afterwards people start leaving the 1st
floor until 6 p.m. From 6 p.m. there are still several detection until
everybody is gone at around 12:30 a.m.
The 1st
floor has most detections in the zones: 1and 4, followed by zone 4. Detection
in zone 1 and 4 follow the general daily pattern of the 1st floor.
Detections in zone 2 follow different pattern. People start coming in at around
9 a.m. with a peak at 12 p.m. and they all leave by 1:30 p.m., with a very few
detections during the rest of the day. There are no detections in zone5,
besides on the 31st of May just before the midday. There are very
few detections in zone 7 and most of them after the midday.
Figure
MC2.1_2. Detections on the 1st floor per zone. In the big view a
daily patterns, in the overview beneath the overall pattern over the two weeks
period.
·
The 2nd floor has
a very regular daily patter with most detections in the zones: 1, 4, 6, 7. In the zone 5 there are no detections. In zone 2 there are
twice as many detections as in zone 3;
Figure
MC2.1_3
·
The 3rd
floor has the least regular daily pattern. In general the most detections are
in zone 1, 4. In the server room there are slightly more detections on the 10th
of June. In zone 5 there are no detections. Zone 2, 3 and 6 follow the same
patterns, only the values for zone 3 are higher than for zone 6. At the
beginning of the 2nd of June zone 1 and 4 have more detections, than
normally at the beginning of the day. Also on the 7th and 8th
of June the number of detections fluctuates differently than on the other days.
Figure
MC2.1_4
·
Weekends: there are four
people (Mbramar, Llagos, Ostrum001, Lcarrara001)
that have been detected during the weekend in the building, but the zones they
visited were their regular working places during the week days.
Figure MC
2.1_5
·
Most employees have fairly
regular behavior, visiting the same zones every day. Some have exactly the same
amount of detections daily being in at the specific zone and floor. We observe
that some employees behave differently, including having more than one prox card or visiting unusual zones, which we describe in
MC2.4.
Figure
MC2.1_6
MC2.2 Describe
up to ten of the most interesting patterns you observe in the building data.
Describe what is notable about the pattern and explain what you can about the
significance of the pattern.
Limit your response to no more than 10 images and
1000 words.
1. Floor 2 zone 12a/b/c (corridors) Lights Power
constantly on, measurements are high during the day and 0 in the weekend. Zone
2 and 6 the highest values, followed by zone 4 and 9, followed by zones 10, 14,
16. Equipment Power follows the same pattern.
Figure MC2.2_1
Figure MC2.2_2
2. The general data has a lot of stable sensor
readings: sensor readings are constant during the whole period for: Cool Schedule
Value, Loop Temp Schedule, Heat Schedule Value, Pump Power, Supply Side Inlet
Mass Flow Rate, Water Heater Setpoint, Supply Side
Outlet Temperature, Water Heater Tank Temperature, Loop Temp Schedule.
Interestingly the Water Heater Setpoint and Loop temp
Schedule have the same value of 60. The Deli-Fan Power, Drybulb
Temp, Supply Side Inlet temp, Supply Side Outlet Temp, Water Heater Tank Temp,
Water Heater Gas Rate have regular patterns for the weekdays and for the
weekends (weekday vs weekend may very).
3. On the 1st floor the Lights Power,
that is constant over de period in zones 3 (main entrance), 8a/b (corridor) and
in the weekends. Also the Equipment
Power is constant in the same zones, while the other zones fluctuate heavily,
being flat in the weekend.
4. We see an interesting pattern for the bathroom
exhaust fan on Sundays (the pattern is regular on the week days). On the 1st
and the 2nd floor on Sundays the fan is using power the whole day
long. On the 3rd floor the fan is off the whole day on both Sundays.
Figure MC2.2_3 Fan power on the 1st
floor.
Figure MC2.2_4 Fan power on the 3rd
floor.
5. The Night cycles are very regular, see figures
MC2.2_Figure
MC2.2_5
Figure MC2.2_6
Figure MC2.2_7
MC2.3 Describe up to ten notable anomalies or unusual
events you see in the data. Describe when and where the event or anomaly occurs
and describe why it is notable. If you have more than ten anomalies to report,
prioritize those anomalies that are most likely to represent a danger or
serious issue for building operation. Limit your response to no more than 10
images and 1000 words.
·
On the 7th and 8th of June
we observe anomalies in many sensor readings in the general data and data on
all the floors, see figures MC2.3_1
MC2.3_7:
o
For the general data: The Electric Demand Power
and The Total Electric Demand show a high peak at 7 a.m. on both days ranging
approximately from 50.000 to 250.000 W and 120.000 to 350.000 W respectively
(comparing to regular patters on other days not higher then approximately
70.000 W); followed by the deviating values during the weekend: higher
measurement values (not higher then approximately 60.000 W) comparing to the
previous weekend (not higher then approximately 130.000 W), see figure MC2.3_1
and MC2.3_2.
o
On the 1st floor many sensor readings
have deviating values. The Reheat Coil
Power shows two high picks during those days (comparing to fairly regular
patters on the other days). Outdoor Air Mass Flow Rate does not fluctuate on
those two days. Cooling COIL Power is constant at the beginning of these two
days. Air Loop Inlet Temp has two peaks on those days. Air Loop Inlet Mass Flow
Rate does not fluctuate on those days. Also CO2 Concentrations are have two
distinct peaks. There are more variables influenced, however we did not find
the relation between those.
o
On the 2nd floor we for example
observe anomalies in zone 8 Thermostat Temp, peaks on 2nd and 8th
of June; op 7th and 8th June constant higher than
average.
o
On the 3rd floor one example anomaly
is Thermostat Temp with two high peaks, and Fan Power with low measurements.
Figure MC2.3_1
Figure MC2.3_2
Figure MC2.3_3
Figure MC2.3_4
Figure MC2.3_5
Figure MC2.3_6
Figure MC2.3_7
·
The anomalies on the 7th and 8th
of June seem to have influence on several sensor readings on the proceeding
weekend (as the values differ from the preceding weekend).
On the 1st floor
the second weekend values are higher than the first weekend values for the
several sensor reading for example: VAV_SYS COOLING COIL Power, VAV_SYS AIR
LOOP INLET Mass Flow Rate, etc. See figure MC2.3_8.
Figure MC2.3_8
·
On the 31st of
May we observe anomalies on the 1st floor in the zone 2: The Lights
Power and the Equipment Power showing a pick in the middle of the day (while
regularly constant around 0 and 400, respectively), see figure MC2.3_9.
Figure MC2.3_9
·
In the general data, the
Wind Direction fluctuates around 50 degrees each day, but on 5th, 8th
and 9th the fluctuations are around 0 and 360 degrees. Also the Wind
Speed shows irregularities with the lower values in the beginning and end of
the measured period, see figure MC2.3_10.
Figure
MC2.3_10
MC2.4 Describe up to
five observed relationships between the proximity card data and building data
elements. If you find a causal relationship (for example, a building event or
condition leading to personnel behavior changes or personnel activity leading
to building operations changes),
describe your discovered cause and effect, the evidence you found to
support it, and your level of confidence in your assessment of the
relationship. Limit your response to no
more than 10 images and 1000 words.
1.
We observe a change in the
data on the 3rd floor on the 2nd of June. From 2nd
of June the Thermostat Temp and Thermostat Heating& Cooling Setpoint in HVAC zone 1 are fluctuating more comparing to
other days, while on the 2nd of June we observed high peaks in zones
1 and 4 around 7-8 a.m. in the prox data.
2.
On the 9th of June
the Reheat COIL Power inHVAC zone 8 is fluctuating
heavily and at the same time we see less detections in the prox
data in zones 1,2,3,4, 6 and no one in the server room.
3.
The weekend are also
interesting. Four of the employees were detected on the weekends: (1)
Lcarrara001, detected on Sunday 5th of June on the 1st
floor in the zones 1 and 4, on the 2nd floor in the zone 2 and on
the 3rd floor in the zones 1, 3, 4 and 6; (2) Ostrum001, detected on
Saturday 11th of June on the 1st floor in the zones 1 and
4, on the 2nd floor in the zone 4 and on the 3rd floor in
the zones 1, 3, 4 and 6; (3) Llagos, detected on
Sunday 12th of June on the 1st floor in the zones 1 and
4, on the 2nd floor in the zone 4 and on the 3rd floor in
the zones 1, 3, 4 and 6; (4) Mbramar, detected on
Saturday 11th of June on the 3rd floor in the zones 1, 4
and 6. All zone detections are regular work places for the employees detected
during the weekend.
In the
weekends the Light Power is on only on the 3rd floor in de HVAC
zones 10 (Sunday 5th of June) and 2, 8 (Saturday, 11th of
June ) and zone 8 (Sunday, 12th of June). Interestingly HVAC zone 2
doesnt correspond to any location in the prox data
where the employees present in the weekend were detected (it corresponds to
zone 2 in the prox data).
4. Most employees have fairly regular behavior,
visiting the same zones every day. Some have exactly the same amount of
detections daily being in at the specific zone and floor. We observe that some
employees behave differently. Few employees seem to have multiple prox cards, like Florez (002 and
003), Unger (001 and 002), Morlun (001 and 002, also
her card has different id: first the last name and then the first later of the
first name, while others have first latter of the first name and then the last
name). Those people have less regular patter as they are detected on different
days with different cards. The prox data of employee Morlun is interesting. The prox
cards of employee Morlun are both detected on the
same days. On Thursday 2nd of June the card 002 is detected at the 1st
floor in the zones 1, 2, 3 and the card 001 at the 2nd floor in the
zones 1, 4, 6, 7. Also employee Morlun has no detections with the card 001 on the day
before, namely on Wednesday 1st of June at the 2nd floor
(while all other days that card has very regular pattern). Interestingly, on
the same day there is difference in the Thermostat Temperature measures on the
2nd floor (where Morlun usually works).